Why is daisychaining multiple extension cords considered unsafe, even if only done to the length of a standard cable?

"never plug extension cords into extension cords" is probably the most common piece of electrical related advice I've ever heard. But if you have, say, 2 x 2m long extension cords, and you plug one into the other, why is that considered a lot more unsafe than just using a single 4 or 5 meter cord?

Does it just boil down to that extra connection creating another opportunity for the prongs to slip out and cause a spark or short circuit? Or is there something else happening there?

For that matter - why aren't super long extension cords (50 or more meters) considered unsafe? Does that also just come down to a matter of only having 2 connections versus 4 or more on a daisy chained cord?

Followup stupid question: is whatever causes piggybacked extension cords to be considered unsafe actually that dangerous, or is it the sort of thing that gets parroted around and misconstrued/blown out of proportion? On a scale from "smoking 20 packs of cigarettes a day" to "stubbing your toe on a really heavy piece of furniture", how dangerous would you subjectively rate daisy chaining extension cords, assuming it was only 1 hop (2 extension cords, no more), and was kept under 5 or 10 metres?

I'm sure there's probably somebody bashing their head against a wall at these questions, but I'm not trying to be ignorant, I'm just curious. Thank you for tolerating my stupid questions

141 comments
  • First, I'm not an electrician, or anything even vaguely approaching one.

    I've never heard that advice with extension cords, only power strips.

    You could theoretically link enough extension cords together to cause problems, but it would need to be some extremely shit extension cords or a LOT of them. Resistance increases over distance, which in power cables manifests as them getting hotter. That isn't a problem until all the sudden it is a problem.

    For power strips, the main danger is that you're potentially introducing more outlets than any of them are rated for. If you're just using 2 3ft power bars to functionally make a 6ft cable that you're only plugging a single thing into.. you're fine. Or at least I was, idk I did it for like a whole year. If you're plugging 16 things into a single wall outlet via power strips you can trip the circuit breaker, or potentially much worse stuff can happen like things getting melty and starting a fire.

    If you know enough of what you're doing to math out the power draw+what your outlet/power strips are rated for you can pretty (afaik) safely daisy chain them if you wanna.

    • Yeah, there are two components here

      1. Adding extra length.
      2. Adding more outlets.

      2 is the main problem, but you need a little of 1 to have it fail in an unsafe way (ie. not just tripping the circuit breaker).

      If you just add a lot of extra outlets and plug lots of stuff in then you will simply trip the circuit breaker. (Assuming that everything is properly set up according to code.) In order to create a problem you need some extra wiring that is rated for less load than the wall wiring. (Now in practice every splitter has some amount of wiring, so these can be the same device, but most power bars are rated to be "fully used" or have a fuse internally). So the problem looks something like this:

      1. Have a 20A wall circuit.
      2. Plug a 10A extension cord into it.
      3. Plug a power bar or other splitter into the extension cord.
      4. Put enough devices into the splitter to generate 15A of current.

      Now you are overloading the extension cord and risking fire.

  • The smart answer: it can start a fire, don't do it.

    The honest answer: I've done it a zillion times and never started a fire. I buy heavy 12 and 10 gauge cords and only chain them to power things that don't require a lot of amps, like LED lights.

    When in doubt, a plug-in power meter is an option you can use to help monitor the situation. Plugs that draw a lot of amps can get warm, even when not using an extension cord. Also, it's not uncommon for a device to pull a lot of amps on initial power-up, and then settle down to a lower draw.

  • I'm not trying to be ignorant, I'm just curious.

    I think you're in the right community! Don't let anyone tell you to shy away from asking curious questions. (well, unless the question is also bigoted, illegal, baiting, sealioning, or otherwise disingenuous)

    I'm not an electrician in any jurisdiction, but one answer for why two 2-meter (~6 ft) extension cords in series is inadvisable compared to a single 4 meter cord is that it's not an apples-to-apples comparison. Longer cords necessarily have to be built differently than shorter cords, not only because of electrical codes (eg the NEC in USA) or product safety specs (eg UL, CSA) but also being well-designed for their expected use. There's also the human aspect, which all good designs must account for as well.

    Here in the USA, common extension cord lengths are 2 m (6 ft), ~7.5 m (25 ft), ~15 m (50 ft), and ~30 m (100 ft). Of those cords, the common wire gauge used might be 18 AWG (1 mm2), 14 AWG (~2 mm2), 16 AWG (1.5 mm^2), and 12 AWG (3.5 mm^2). I've intentionally rounded the metric units so they're more analogous to common wire gauges outside the USA. Finally, the insulation used can be anything from "thin, indoor only" to "heavy, abrasion and sunlight resistant". And while the USA technically has a boat-load of AC connectors, the grand majority will use the standard 2-pin or 3-pin 120v connector, formally known as NEMA 1-15 and NEMA 5-15 respectively. What this means is that chaining extension cords is both possible and somewhat common. The problem is one of mismatched designs.

    From a cursory search on the website of a major USA home improvement store, the smallest wire gauge used for a 100 ft cable is 16 AWG. The largest is 10 AWG (nb: smaller numbers mean bigger wire). That thinner cable is marketed for outdoor use. The thicker cable indicates its use "indoor/outdoor" and for heavy-duty applications. It is also branded with a major power-tool company, which would be appropriate as power tools often draw high current.

    Whereas looking at 6 ft extension cords, most are 16 AWG but a few were 18 AWG (thinner than 16) or 14 AWG (thicker). But I could not find any thicker cables than that, certainly nothing that uses 10 AWG (~6 mm^2). The "heavy duty" cables of this length also used only 16 AWG wire.

    Because electrical resistance is additive in series, and because Ohm's Law governs the voltage lost at the end of a cord, the use of insufficiently large conductors can cause voltage issues for high-current appliances. Appliances for USA-spec generally require 120 Volts +/- 10%, with utilities aiming to provide 120 Volts +/- 5% from the outlets. This means a "sufficient" power cord should not have a voltage drop of more than 6 volts, give or take. Of course, a high-current appliance will also cause a larger voltage drop than a low-current device, so we only consider the former case.

    For a machine that draws 12 Amps attached to a 100 ft extension cord made of 18 AWG wire, the voltage drop would be 15 volts. This is bad for the machine, which now sees a lower voltage than expected. Had the cord been made of 12 AWG wire, the drop is an acceptable 3 volts.

    So if you're operating construction tools, it would be a terrible idea to use three random 6-ft cables, and you should instead use a single 25-ft cable. Even though it's longer than you need, the fact is that most 25 ft cables use thicker conductors, which reduces the voltage drop overall.

    But there's also that peaky human factor. Sure, there would also be more connectors which could come loose, but the really pressing issue with daisy chained cords is when people do that indoors, because they only have light-duty 6 ft cables handy. And for that Christmas tree, they need to use attach three cables together to go beneath the hallway rug.

    This is essentially the worst-case scenario: using thin conductor cords, with thin insulation, underneath very flammable household surfaces, which are also trodden upon by foot traffic. Every step on that cord weakens the insulation and fatigues the conductors. Over time, the conductor becomes thinner where it's being fatigued, and this increases the voltage drop. An unfortunate result of a voltage drop is that it generates heat. For a cable which is uniformly thin, this heat is spread over the whole length. But for localized conductor damage, the heat is pin-point... directly under a flammable rug.

    In the USA, some 3300 house fires started from an extension cord. Because these cords are not within the walls, they are usually beyond the control of often-strict building/electrical codes, something that's been critiqued by a prominent YouTuber. The US CPSC even goes so far as to create memes to promote their messaging that space heaters -- a common, high-current appliance -- should not be used with extension cords or strips.

    Of course, from an electrical perspective, even a ten-long chain of dinky extension cords would have no problem powering just a single LED night light. But it's reasonable to ask: 1) is this just asking to be struck down by fate, 2) are there better alternatives like thicker/longer cords, and 3) why isn't there an outlet where you need it?

    (There's also a scenario where too long or thin of an extension cord can cause a circuit breaker to fail to trip during a short circuit, but it's fairly esoteric and this post is quite long now)

    In short, the blanket recommendation to avoid daisy-chaining cords is to avoid the nasty and sometimes fatal results when that can go wrong, even with it might not always play out that way. There's almost always something safer than can be done than daisy chaining.

  • Connectors come loose, which makes them dangerous.

    They are uninsulated points that allow water and material ingress, and can partially or fully pull apart, causing arching. Which can cause combustion.

    This is the main reason these are dangerous, which the majority of this entire thread misses. The added length or connector resistance is somewhat negligible here unless you're daisy chaining long conductors, which often isn't the case for in-home extensions.

  • On a scale from "smoking 20 packs of cigarettes a day" to "stubbing your toe on a really heavy piece of furniture", how dangerous would you subjectively rate daisy chaining extension cords

    As dangerous as one extension cord of their combined length. Don't forget to verify that every cord rating is above load rating. I recommend to use at least same rating as circuit breaker or get extension cord with circuit breaker built in and never decrease rating down the line without circuit breaker before it, so even if you somehow overload it, there will be protection from it.

    AND NEVER COIL OR THERMALY INSULATE! Cords rely on convection for heat dissipation, and spooling and insulating reduces it, thus increasing electrical insulator temperature until it melts and spontaneously combusts. This applies to extension cords in general.

  • I think a lot of people are mostly on the money here. It's to do with resistance. Now, I'm not a qualified electrician, but I'm an amateur radio license holder and a lot of what you learn for that is applicable here.

    The main problem as many have said is resistance. This comes about from both the length of the conductors but also from every plug/socket connection adds resistance. Also in the case of the non extension socket multipliers, as you add more the weight bearing down would also likely start to make the connections less secure causing more resistance and possibly adding to the problem through arcing.

    Now the resistance alone on small loads likely wouldn't be a huge problem. But if you had a large enough load (specifically at the end of the stacked connectors/extensions), or a fault that caused a larger than expected load the current would cause the resistance to generate heat.

    There's a lot of ifs and maybes involved, but really why do it? There's really no real world situation to need to have a dangerous amount of extensions like this though.

    For larger loads here in the UK there's some very specific other concerns when dealing with ring mains. But really you'd need to do really weird/unusual things for that to become a problem.

  • Extension cords are rated for certain levels of resistive load based on their length. It typically has to do with the gauge of the wire used in the chord itself. Electrical resistance is typically converted into heat energy. If you daisy chain extension cords and have them plugged into appliances, then the resistive load of the chained cords can be higher than the rating of one or more of the extension cords. This can cause fire.

  • The longer the cord is the more resistance there is; ie the more electrical load on the circuit. As long as you are pulling less than what the circuit and cord is rated for, there isn't an issue, you will just be wasting a little extra power from the extra resistance. The plugs themselves can also have a bit of extra resistance.

    Two pieces of advice that will make the biggest difference:

    • Keep the total length of all extension cables used as short as is reasonable. Don't use a 20m cable when a 4m cable will do.
    • Buy extension cords with higher wire gauges (higher wire thicknesses). A 12 gauge cable (4mm2) will provide notably less resistance than a 14 (2.5mm2) or 16 gauge cable (1.5mm2). The packaging will say what gauge it is. Note, I'm talking about the thickness of the metal itself, not the thickness of the extension cord as a whole. I have seen some very, very thick extension cords with absolute trash wires inside.
141 comments